What are Louvred Fire Doors?
Louvred steel fire doors are fire rated steel door sets that incorporate certified fire resistant louvre panels to allow controlled airflow while maintaining compartmentation. They are specifically designed for areas where ventilation is required but fire separation must not be compromised.
Tested to standards such as BS EN 1634-1 (and EN 16034 where externally installed), these doors provide defined fire resistance periods, typically 30, 60, 90, or 120 minutes. The louvre system itself must be fire rated and included within the tested door configuration to ensure the declared fire performance is maintained.
Louvred steel fire doors are commonly installed in plant rooms, boiler rooms, electrical intake rooms, and mechanical service areas. They provide essential ventilation for equipment and services while supporting compliance with Building Regulations and the buildingโs fire strategy.
When supplied and installed as a complete certified door set, louvred steel fire doors deliver reliable fire protection, durability, and controlled airflow in demanding commercial and industrial environments.
Louvred Fire Door Information and Buying Guide
Types of Louvred Fire Doors
Types of Louvred Fire Doors
Louvred steel fire doors are available in several configurations depending on fire resistance period, ventilation requirements, and application. All fire-rated versions must be supplied as certified door sets tested to BS EN 1634-1 (and EN 16034 where externally installed).
By Fire Resistance Rating
FD30 Louvred Steel Fire Doors
Provide 30 minutes of fire resistance and are commonly specified in lower-risk commercial plant and service areas.
FD60 Louvred Steel Fire Doors
Offer 60 minutes of fire protection and are widely used in industrial buildings and higher-risk service spaces.
FD90 / FD120 Louvred Steel Fire Doors
Designed for environments requiring extended fire compartmentation, such as large plant rooms or critical infrastructure spaces.
Fire and Smoke Rated Louvred Doors (FD30S / FD60S)
These doors combine fire resistance with smoke control, incorporating certified smoke seals in addition to fire rated louvre systems.
High Free Area Ventilation Doors
Some louvred fire doors are designed to provide greater airflow capacity while maintaining certified fire performance. The free air area is determined by the tested louvre system.
Internal vs External
Louvred Steel Fire Doors
Internal doors โ Tested to BS EN 1634-1 for compartmentation within buildings.External doors โ Must also comply with EN 16034 and BS EN 14351-1, covering weather resistance, air permeability, and wind load.
Single and Double Leaf Configurations
Available as:
- Single leaf doors for standard service rooms
- Double leaf doors for larger plant areas or equipment access
Security Rated Louvred Steel Fire Doors
Where enhanced protection is required, security rated options (e.g. LPS 1175 or PAS24) may be available, provided the fire and ventilation certification remains valid.
Each type must be specified within the scope of its certified test evidence, ensuring both fire performance and ventilation requirements are achieved without compromising compliance.
Design & Customisation
Design & Customisation
Louvred steel fire doors can be configured to meet ventilation, fire resistance, and security requirements, provided all elements remain within the scope of the certified test evidence (typically BS EN 1634-1, and EN 16034 / BS EN 14351-1 where externally located).
Fire Resistance Rating
Available in certified ratings such as:
- FD30 (30 minutes)
- FD60 (60 minutes)
- FD90 / FD120 (where required)
Smoke control variants (FD30S / FD60S) can be specified where cold smoke restriction is required.
Louvre Configuration
The ventilation panel can be customised in terms of:
- Size and position within the door leaf (subject to certification limits)
- Free air area to suit airflow requirements
- Single or multiple louvre sections
The louvre system must be a certified fire-rated unit approved for use within the specific door set.
Insulation and Thermal Performance
For external doors, insulated cores can be specified to improve thermal efficiency and meet project U value targets.
Door Configuration
- Single leaf doors
- Double leaf doors for wider plant or equipment access
- Optional overpanels or side panels (where certified)
All doors are manufactured to measure.
Finish and Colour
Steel door leaves and frames can be powder coated in a wide range of colours to match the building exterior or internal design.
Hardware and Ironmongery
Customisable options include:
- Lever handles and locksets
- Panic bars or emergency exit devices
- Door closers
- Access control integration
- Electromagnetic hold-open devices
- Multi-point locking systems
All hardware must be fire rated and compatible with the certified configuration.
Security Enhancements
Security-rated options (e.g. LPS 1175 or PAS24) can be specified where additional forced-entry resistance is required, provided this does not compromise fire certification.
Accessibility Options
Customisation may include:
- Low thresholds
- Adjustable frames
- Automatic operators (where compatible with the fire strategy)
It is essential that any design modifications remain within the manufacturerโs tested scope to ensure continued compliance with fire performance, ventilation certification, and building regulations.
Applications
Applications
Louvred steel fire doors are specified where certified fire resistance and controlled ventilation are required within the same opening. They are commonly used in technical and service environments where equipment requires airflow but compartmentation must be maintained.
Plant Rooms
Installed in:
- Mechanical plant rooms
- HVAC rooms
- Generator rooms
They allow airflow for cooling equipment while maintaining the required fire resistance period.
Boiler Rooms
Boiler and heating plant areas often require permanent ventilation. Fire rated louvred doors provide airflow without compromising fire separation.
Electrical Intake and Switch Rooms
Used in:
- Electrical substations
- Switchgear rooms
- Transformer enclosures
Ventilation helps dissipate heat from electrical equipment while maintaining certified fire performance.
Industrial Facilities
Commonly fitted in:
- Production plants
- Service corridors
- Maintenance areas
Steel construction provides durability in demanding environments.
Commercial Buildings
Specified in:
- Service risers
- Back-of-house areas
- Building management rooms
They support compartmentation in accordance with the buildingโs fire strategy.
Healthcare and Public Buildings
Installed in technical and service areas where airflow is required but fire protection remains essential.
External Plant Enclosures
Externally located plant areas may require doors compliant with BS EN 16034 and BS EN 14351-1, providing both fire resistance and weather performance.
Louvred steel fire doors are selected where maintaining ventilation for equipment and services is critical, while still achieving certified fire compartmentation and regulatory compliance.
Features & Benefits
Features & Benefits
Louvred steel fire doors are designed to combine certified fire resistance with controlled airflow, making them suitable for plant and service environments where ventilation is essential.
Certified Fire Resistance
Tested to BS EN 1634-1 (and EN 16034 where externally located), louvred steel fire doors provide defined fire resistance periods such as FD30, FD60, FD90, or FD120, maintaining compartmentation in line with Building Regulations.
Integrated Fire Rated Ventilation
Incorporating certified fire rated louvre panels, these doors allow controlled airflow for:
- Cooling plant equipment
- Ventilating boiler rooms
- Managing heat in electrical rooms
Ventilation is achieved without compromising fire integrity.
Robust Steel Construction
Manufactured from heavy duty steel, these doors offer durability and impact resistance in high use or industrial environments.
Smoke Control Options
Available as FD30S or FD60S, incorporating smoke seals to restrict cold smoke movement where required by the fire strategy.
External Performance (Where Required)
Externally located versions can be fully compliant with EN 16034 and BS EN 14351-1, providing weather resistance, wind load performance, and air permeability ratings.
Security Enhancements
Steel construction provides strong resistance to forced entry. Security-rated upgrades (e.g. LPS 1175) may be available where additional protection is required.
Compatible with Access Control
Louvred fire doors can integrate with:
- Panic hardware
- Door closers
- Access control systems
- Electromagnetic hold-open devices
All hardware must remain within the certified configuration.
Long Service Life and Low Maintenance
Powder coated steel finishes and robust louvre systems are designed for durability, reducing ongoing maintenance requirements.
These features make louvred steel fire doors an effective solution for technical and service areas where airflow, durability, and certified fire protection must operate together.
Compliance & Safety
Compliance & Safety
Louvred steel fire doors are regulated fire safety products and must comply with fire resistance standards, product certification requirements, and Building Regulations. Because the louvre forms part of the fire barrier, it must be certified within the tested door configuration.
Fire Resistance โ BS EN 1634-1
Internal louvred steel fire doors must be tested to BS EN 1634-1, confirming:
- Integrity (E) โ Resistance to flame penetration
- Insulation (EI) โ Heat transfer limitation (where specified)
- Declared fire resistance periods (e.g. 30, 60, 90, 120 minutes)
The louvre panel must be a fire-rated system included within the test evidence. Standard non-rated ventilation grilles cannot be retrofitted into fire doors.
Smoke Control (Where Required)
Where smoke restriction is required, doors must be specified as FD30S or FD60S and include certified smoke seals in addition to the fire-rated louvre system.
External Compliance โ EN 16034 and BS EN 14351-1
If the louvred steel fire door is installed externally, it must also comply with:
- EN 16034 โ Fire resisting and/or smoke control characteristics
- BS EN 14351-1 โ External pedestrian doorsets
- The door must be CE and UKCA marked, with a Declaration of Performance confirming fire and external performance characteristics.
Building Regulations โ Approved Document B
Louvred steel fire doors must align with the buildingโs fire strategy and comply with Approved Document B, including:
- Correct fire resistance period
- Installation within designated compartment walls
- Protection of escape routes and plant areas
Emergency Exit Hardware Standards (If Applicable)
Where forming part of a means of escape, hardware must comply with:
- BS EN 1125 โ Panic exit devices (public buildings)
- BS EN 179 โ Emergency exit devices (staff only areas)
- All ironmongery must be approved for use within the certified door set.
Installation to Certified Detail
Installation must follow the manufacturerโs tested detail, including:
- Approved fixing methods
- Correct gap tolerances
- Compatible seals and hardware
- Certified louvre positioning and size
Unauthorised alterations can invalidate fire certification.
Ongoing Inspection and Maintenance
Louvred steel fire doors must be included in routine fire door inspections to ensure:
- Self-closing and latching function
- Integrity of seals
- Secure and undamaged louvre panels
- Correct operation of hardware
When correctly specified, installed, and maintained in accordance with BS EN 1634-1 (and EN 16034 where external), louvred steel fire doors provide compliant fire compartmentation while allowing essential ventilation for plant and service environments.
Installation & Maintenance
Installation & Maintenance
Louvred steel fire doors must be installed and maintained strictly in accordance with their certified test evidence. Because the louvre panel forms part of the fire-resisting construction, installation quality is critical to maintaining compliance.
Installation Requirements
Install as a Complete Certified Doorset
Louvred steel fire doors must be supplied and installed as a fully certified door set, including:
- Steel door leaf
- Frame
- Certified fire-rated louvre panel
- Intumescent (and smoke) seals
- Approved hinges and hardware
- Door closer
All components must match the configuration tested to BS EN 1634-1 (and EN 16034 / BS EN 14351-1 if external).
Certified Louvre Integration
The louvre panel must:
- Be a tested fire rated unit
- Be positioned and sized in accordance with certification
- Be installed using approved glazing beads or fixing systems
- Standard ventilation grilles must never be retrofitted into a fire door.
Structural Fixing
The frame must be securely fixed into a suitable fire-rated wall construction (masonry, concrete, or steel stud) using the approved fixing method and spacing.
Gap Tolerances and Alignment
Correct gap tolerances between leaf and frame must be maintained. Excessive clearances can compromise fire and smoke performance. The door must operate smoothly and latch fully.
Self Closing Devices
Where required by the fire strategy, a compliant door closer must be installed and adjusted to ensure reliable self closing and latching.
Hardware and Alarm Integration
If fitted with panic hardware, access control, or hold open devices:
- All components must be fire-rated
- Installation must not compromise door integrity
- Hold open devices must release automatically upon fire alarm activation
Supply Only Considerations
Supply only louvred steel fire doors may be provided to competent contractors; however:
- Accurate measurements are essential
- Installation must follow certified instructions exactly
- Compliance responsibility rests with the installer and building operator
- Professional installation is strongly recommended in commercial and public buildings.
Maintenance Requirements
Routine Inspection
- Regular checks should confirm:
- Door self-closes and latches correctly
- Intumescent and smoke seals are intact
- Louvre panel is secure and undamaged
- Hinges and hardware are firmly fixed๐ฌ Louvre Condition
Inspect the louvre assembly for:
- Damage or distortion
- Loose fixings
- Obstruction from debris
Any repair must use approved components to maintain fire certification.
Periodic Servicing
In commercial environments, annual fire door inspections are recommended at minimum, with more frequent checks in high use plant areas.Maintenance may include:
- Closer adjustment
- Seal replacement
- Hardware tightening
- Latch engagement testing
Ongoing Compliance
Louvred steel fire doors must be included in the buildingโs fire risk assessment and ongoing safety management plan. Any modification outside the certified scope can invalidate fire performance.
When correctly installed and maintained, louvred steel fire doors provide compliant fire compartmentation while delivering essential ventilation in technical and service environments.
Price Guide
Price Guide
The cost of louvred steel fire doors depends on the fire resistance period, size of the door, louvre free air area, configuration (single or double leaf), hardware specification, and whether the door is internal or external. Because the louvre panel must be a certified fire-rated system, this adds to the base fire door cost.
FD30 Louvred Steel Fire Doors (30 Minute Rating)
Suitable for standard plant and service areas.
- Supply only: From ยฃ1,100 โ ยฃ1,700
- Supplied and installed: From ยฃ1,800 โ ยฃ2,800
FD60 Louvred Steel Fire Doors (60 Minute Rating)
Commonly specified for higher-risk commercial and industrial plant rooms.
- Supply only: From ยฃ1,400 โ ยฃ2,100
- Supplied and installed: From ยฃ2,200 โ ยฃ3,500
FD90 / FD120 Louvred Steel Fire Doors
Used in critical infrastructure and larger plant areas requiring extended fire resistance.
- Supply only: From ยฃ2,000 โ ยฃ3,000
- Supplied and installed: From ยฃ3,200 โ ยฃ5,000+
Louvre Size Impact
Smaller certified louvre panels are typically included within the base range.Larger ventilation areas or multiple louvre sections may add:
- ยฃ400 โ ยฃ1,200+, depending on airflow requirements and certification limits.
Fire and Smoke Rated (FD30S / FD60S)
Where smoke seals are required, expect an additional:
- ยฃ150 โ ยฃ400, depending on specification.
Security Rated Louvred Steel Fire Doors
Where combined fire and security certification (e.g. LPS 1175) is required:
From ยฃ3,500 โ ยฃ6,500+ installed, depending on configuration and rating level.
External Compliance (EN 16034 / BS EN 14351-1)
Externally located louvred steel fire doors with full CE/UKCA marking may sit toward the higher end of the pricing range due to additional weather performance requirements.
What Affects the Final Cost
- Fire resistance period
- Louvre free air area
- Single or double leaf configuration
- Panic hardware or access control
- Powder-coated finish
- Installation complexity and structural preparation
- External performance compliance (where applicable)
Getting an Accurate Quote
Because louvred steel fire doors must be installed as certified door sets to maintain compliance with BS EN 1634-1 (and EN 16034 where external), a detailed site survey or accurate opening measurements are recommended. This ensures the correct fire rating, ventilation performance, and hardware specification for full regulatory compliance.
Quick Quotes
Whether you get a quote online or through contacting our team, you'll be sure to receive your quote promptly.
Price Transparency
Fair pricing ensures you know exactly what youโre paying for, with no hidden costs or markups. Trade enquiries welcome.
Supply & Installation
Whether you're looking for expert installation or supply only. We offer that on all of our products.
Rated 5 Stars
We are rated 5 stars for our customer service and product quality - for your peace of mind. Just check out our latest reviews.
Frequently Asked Questions - Louvered Fire Doors
1. What are fire rated louvred steel doors used for?
1. What are fire rated louvred steel doors used for?
Fire rated louvred steel doors are used in areas where both fire protection and ventilation are required. They are commonly installed in plant rooms, boiler rooms, service areas, corridors, and external openings where airflow is essential but fire resistance must be maintained.
2. How much fire protection do louvred steel doors provide?
2. How much fire protection do louvred steel doors provide?
These doors are tested and certified to provide up to 120 minutes (E120) of fire resistance. This means they can help contain fire and protect escape routes for a significant period, supporting building safety and compliance.
3. Do louvred panels reduce the fire performance of the door?
3. Do louvred panels reduce the fire performance of the door?
No. Fire rated louvred doors are specifically engineered so that the louvre sections maintain the overall fire rating. They are tested as a complete doorset to ensure both ventilation and fire protection work together safely.
4. How much airflow do fire rated louvred doors allow?
4. How much airflow do fire rated louvred doors allow?
These doors are designed to provide high levels of ventilation, with some configurations offering up to around 50% free airflow. This makes them ideal for environments that require constant air movement without compromising safety.
5. Can fire rated louvred steel doors be customised?
5. Can fire rated louvred steel doors be customised?
Yes. They are made to order and can be supplied in single or double door configurations, with different louvre sizes, locking options, and a wide range of powder coated finishes to suit the application.

